Описание оборудования | |
---|---|
G10 ultra-compact module 1 input and 1 output | |
General specifications | |
Slave type | A/B slave |
AS-Interface specification | V3.0 |
Required master specification | ? V2.1 |
UL File Number | E223772 "For use in NFPA 79 Applications only" |
Indicators/operating means | |
LED FAULT | error display; LED red red: communication error or address is 0 red flashing: overload of sensor power supply or overload of outputs or external auxiliary voltage UAUX missing |
LED AS-i | AS-Interface voltage; LED green |
LED IN | switching state (input); LED yellow |
LED OUT | Switching state (output); LED yellow |
Electrical specifications | |
Auxiliary voltage | 20 ... 30 V DC PELV |
Rated operating voltage | 18.5 ... 31.6 V from AS-Interface |
Rated operating current | ? 40 mA / max. 60 mA |
Protection class | III |
Surge protection | UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV) |
Input | |
Number/Type | 1 input for 2- or 3- wire sensors (PNP), DC |
Supply | from external auxiliary voltage UAUX |
Voltage | 20 ... 30 V |
Current loading capacity | ? 1000 mA overload and short-circuit resistant |
Input current | ? 9 mA (limited internally) |
Switching point | according to DIN EN 61131-2 (Type 2) |
Signal delay | < 1 ms (input/AS-Interface) |
Output | |
Number/Type | 1 electronic output, PNP, |
Supply | from external auxiliary voltage UAUX |
Voltage | ? (UAUX - 0.5 V) |
Current loading capacity | ? 1000 mA overload and short-circuit resistant |
Directive conformity | |
Electromagnetic compatibility | |
Standard conformity | |
Degree of protection | EN60529:2000 |
Fieldbus standard | EN62026-2:2013 |
Input | EN 61131-2:2007 |
Emitted interference | EN61000-6-4:2007 |
AS-Interface | EN62026-2:2013 |
Noise immunity | EN61000-6-2:2005, EN61326-1:2006, EN62026-2:2013 |
Programming instructions | |
Profile | S-7.A.E |
IO code | 7 |
ID code | A |
ID1 code | 7 |
ID2 code | E |
Data bits (function via AS-Interface) | input output |
Parameter bits (programmable via AS-i) | function |
Approvals and certificates | |
UL approval | cULus Listed, Type 1 enclosure |
Ambient conditions | |
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |